Main: 34 × 17 Christie MicroTiles 1.25 S70
- Size
- 8.16 × 4.59 m
- Diagonal
- 369 in
- Area
- 37.5 m²
- Resolution
- 6,528 × 3,672 px
- Pixels
- 23.97 M px
- Panels
- 578 + 29 spares
- Weight
- 1,272 kg panels only
- Power
- 28.9 kW max, 11.6 kW typical, 12 circuits
- Data
- 68 runs on 14 processors at 60 Hz 8-bit
This is a live example. Change the panel and the size in the steps and every figure recomputes.
| Main | Christie MicroTiles 1.25 S70 | 34 × 17 | 8.16 × 4.59 m · 369 in | 6,528 × 3,672 px | wall-mounted |
- Panels
- 578 + 29 spares
- Weight
- 1,272 kg panels only
- Power
- 28.9 kW max, 11.6 kW typical, 12 circuits
- Data
- 68 runs on 14 processors at 60 Hz 8-bit
The install list, the data wiring and power run plans, the cable tags and the system sheet print with a Solo account: rigplan.app/pricing
Data wiring 68 runs · up to 12 panels per run at 80% · worst 57% · 14× NovaStar VX1000 · fed from the top
Display connection file 🔒 The file NovaLCT loads under Screen Connection, Load from File; the receiving card file still comes from the maker.
| Run 1 | Column 1, rows 1 to 9 | 9 panels · 57% of port |
| Run 2 | Column 1, rows 10 to 17 | 8 panels · 51% of port |
| Run 3 | Column 2, rows 1 to 9 | 9 panels · 57% of port |
| Run 4 | Column 2, rows 10 to 17 | 8 panels · 51% of port |
| Run 5 | Column 3, rows 1 to 9 | 9 panels · 57% of port |
| Run 6 | Column 3, rows 10 to 17 | 8 panels · 51% of port |
| Run 7 | Column 4, rows 1 to 9 | 9 panels · 57% of port |
| Run 8 | Column 4, rows 10 to 17 | 8 panels · 51% of port |
| Run 9 | Column 5, rows 1 to 9 | 9 panels · 57% of port |
| Run 10 | Column 5, rows 10 to 17 | 8 panels · 51% of port |
| Run 11 | Column 6, rows 1 to 9 | 9 panels · 57% of port |
| Run 12 | Column 6, rows 10 to 17 | 8 panels · 51% of port |
| Run 13 | Column 7, rows 1 to 9 | 9 panels · 57% of port |
| Run 14 | Column 7, rows 10 to 17 | 8 panels · 51% of port |
| Run 15 | Column 8, rows 1 to 9 | 9 panels · 57% of port |
| Run 16 | Column 8, rows 10 to 17 | 8 panels · 51% of port |
| Run 17 | Column 9, rows 1 to 9 | 9 panels · 57% of port |
| Run 18 | Column 9, rows 10 to 17 | 8 panels · 51% of port |
| Run 19 | Column 10, rows 1 to 9 | 9 panels · 57% of port |
| Run 20 | Column 10, rows 10 to 17 | 8 panels · 51% of port |
| Run 21 | Column 11, rows 1 to 9 | 9 panels · 57% of port |
| Run 22 | Column 11, rows 10 to 17 | 8 panels · 51% of port |
| Run 23 | Column 12, rows 1 to 9 | 9 panels · 57% of port |
| Run 24 | Column 12, rows 10 to 17 | 8 panels · 51% of port |
| Run 25 | Column 13, rows 1 to 9 | 9 panels · 57% of port |
| Run 26 | Column 13, rows 10 to 17 | 8 panels · 51% of port |
| Run 27 | Column 14, rows 1 to 9 | 9 panels · 57% of port |
| Run 28 | Column 14, rows 10 to 17 | 8 panels · 51% of port |
| Run 29 | Column 15, rows 1 to 9 | 9 panels · 57% of port |
| Run 30 | Column 15, rows 10 to 17 | 8 panels · 51% of port |
| Run 31 | Column 16, rows 1 to 9 | 9 panels · 57% of port |
| Run 32 | Column 16, rows 10 to 17 | 8 panels · 51% of port |
| Run 33 | Column 17, rows 1 to 9 | 9 panels · 57% of port |
| Run 34 | Column 17, rows 10 to 17 | 8 panels · 51% of port |
| Run 35 | Column 18, rows 1 to 9 | 9 panels · 57% of port |
| Run 36 | Column 18, rows 10 to 17 | 8 panels · 51% of port |
| Run 37 | Column 19, rows 1 to 9 | 9 panels · 57% of port |
| Run 38 | Column 19, rows 10 to 17 | 8 panels · 51% of port |
| Run 39 | Column 20, rows 1 to 9 | 9 panels · 57% of port |
| Run 40 | Column 20, rows 10 to 17 | 8 panels · 51% of port |
| Run 41 | Column 21, rows 1 to 9 | 9 panels · 57% of port |
| Run 42 | Column 21, rows 10 to 17 | 8 panels · 51% of port |
| Run 43 | Column 22, rows 1 to 9 | 9 panels · 57% of port |
| Run 44 | Column 22, rows 10 to 17 | 8 panels · 51% of port |
| Run 45 | Column 23, rows 1 to 9 | 9 panels · 57% of port |
| Run 46 | Column 23, rows 10 to 17 | 8 panels · 51% of port |
| Run 47 | Column 24, rows 1 to 9 | 9 panels · 57% of port |
| Run 48 | Column 24, rows 10 to 17 | 8 panels · 51% of port |
| Run 49 | Column 25, rows 1 to 9 | 9 panels · 57% of port |
| Run 50 | Column 25, rows 10 to 17 | 8 panels · 51% of port |
| Run 51 | Column 26, rows 1 to 9 | 9 panels · 57% of port |
| Run 52 | Column 26, rows 10 to 17 | 8 panels · 51% of port |
| Run 53 | Column 27, rows 1 to 9 | 9 panels · 57% of port |
| Run 54 | Column 27, rows 10 to 17 | 8 panels · 51% of port |
| Run 55 | Column 28, rows 1 to 9 | 9 panels · 57% of port |
| Run 56 | Column 28, rows 10 to 17 | 8 panels · 51% of port |
| Run 57 | Column 29, rows 1 to 9 | 9 panels · 57% of port |
| Run 58 | Column 29, rows 10 to 17 | 8 panels · 51% of port |
| Run 59 | Column 30, rows 1 to 9 | 9 panels · 57% of port |
| Run 60 | Column 30, rows 10 to 17 | 8 panels · 51% of port |
| Run 61 | Column 31, rows 1 to 9 | 9 panels · 57% of port |
| Run 62 | Column 31, rows 10 to 17 | 8 panels · 51% of port |
| Run 63 | Column 32, rows 1 to 9 | 9 panels · 57% of port |
| Run 64 | Column 32, rows 10 to 17 | 8 panels · 51% of port |
| Run 65 | Column 33, rows 1 to 9 | 9 panels · 57% of port |
| Run 66 | Column 33, rows 10 to 17 | 8 panels · 51% of port |
| Run 67 | Column 34, rows 1 to 9 | 9 panels · 57% of port |
| Run 68 | Column 34, rows 10 to 17 | 8 panels · 51% of port |
Power runs 12 circuits · up to 51 panels/circuit · 28.9 kW max · 1× distro
| Circuit 1 | Columns 1 to 3, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L1 |
| Circuit 2 | Columns 4 to 6, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L2 |
| Circuit 3 | Columns 7 to 9, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L3 |
| Circuit 4 | Columns 10 to 12, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L1 |
| Circuit 5 | Columns 13 to 15, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L2 |
| Circuit 6 | Columns 16 to 18, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L3 |
| Circuit 7 | Columns 19 to 21, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L1 |
| Circuit 8 | Columns 22 to 24, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L2 |
| Circuit 9 | Columns 25 to 27, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L3 |
| Circuit 10 | Columns 28 to 30, snake up and down, hops right | 51 panels · 2,550 W · 87% · Distro 1 · L1 |
| Circuit 11 | Columns 31 to 32, snake up and down, hops right | 34 panels · 1,700 W · 58% · Distro 1 · L2 |
| Circuit 12 | Columns 33 to 34, snake up and down, hops right | 34 panels · 1,700 W · 58% · Distro 1 · L3 |
| Patch | Distro 1: circuits 1 to 12 (L1×4 L2×4 L3×4) | |
The rules behind every number
Every quantity above is derived from the rules below, written with working AV techs and corrected as they red-pen them.
- openSpare panels: 5% of wall count, minimum 2 (wall-mounted, spares kept on site at the one-off rate).
- ✓ confirmedWall-mounted: the wall or structure carries the panels, 1,272 kg over 8.16 × 4.59 m, about 34 kg/m² plus your fixing hardware. Nothing hangs from the panels, so the hang limit does not apply. The structure is designed for the site and is not derived here; no bumpers, points, ground support, distros, cases or truck are listed.
- ✓ confirmedCircuits sized on max load (full white) at 80% derate: 58 panels per 16 A / 230 V circuit (50 W/panel). Typical draw shown separately for the venue/generator ask.
- ✓ confirmedPower runs follow the connectors: in one side, out the other, gendered plugs, jumpers as short as the maker can get away with. Vertical works both ways, sideways only one hop to the right (rear view), so a run may snake up and down across adjacent columns, but never left and right. Vertical snakes over 3 columns need 12 circuits (single columns would need 34, full rows 17).
- openPower for a permanent install comes as 12 house circuits from the building's distribution board; no distro or feeders are listed. TRUE1 jumpers = panels − runs, +10% spare.
- ✓ confirmedRuns are load-balanced: panels split evenly across the circuits a shape needs (12+12, never 18+6) so every main-in pulls about the same. Phases are a suggested round-robin L1 to L3 within each distro.
- ✓ confirmedExact-pixel mapping (NovaStar VX1000): a port carries only the panels wired to it, and data snakes in any direction (unlike power). Wiring follows whole columns as vertical serpentines, numbered from the left seen from the rear, the natural reading order when patching, with every run capped at 80% of 650 k px per 1G port at 60 Hz 8-bit (threshold, refresh and depth adjustable): at most 12 panels per run, giving 68 runs, each looped back to a B port on a second unit, worst run 57%. Loads balance evenly across runs. Capacity is the sheet figure at 8-bit; refresh scales as 60/Hz. No sheet publishes a per-port width cap; the MX40 Pro’s minimum load width is applied where it bites. Correct me with measured figures.
- ✓ confirmedRedundancy defaults off. Rental shows rarely run looped data; it is primarily a critical-installation feature. Turning it on gives every run a B loop from a second unit, so the processor count doubles.
- openData enters each run at the top of its first column and snakes on from there, so the drawing, the cable tags and the connection file all start at that end. The entry end is a choice per wall; the runs, ports and processors stay the same either way.
- openHome runs cut at run distance + wall height + 5 m service loop.
- openProcessors are checked on two limits: port count and total pixel capacity (capacities placeholder).
- ✓ confirmedProcessor list defaults to NovaStar (VX1000 first, UHD Jr / MCTRL / MX / VX family). Rental houses rarely run Brompton; it stays available for the shops that do. All figures verified against manufacturer spec sheets.
- openElectronics spares: 1 receiving card per 25 panels, 1 PSU per 25, minimum 1 each.
Cable tags 1224 tags · 68 data runs · 12 circuits
One label per cable, both ends named, in the order the runs are wired: cabinets as column and row seen from the rear, c1r1 top left. Print them, or copy the list as CSV for a label printer.
Copy tags as CSV 🔒The tag list, your own label format, and the CSV for a label printer are a Solo feature.
Panels 0/4 done
| 578 pcs | Christie MicroTiles 1.25 S70 tiles | 34×17 wall, 8.2×4.6 m | ||
| 29 pcs | Spare tiles | one-off rate 5% | ||
| 24 pcs | Spare receiving cards | |||
| 24 pcs | Spare PSUs |
Rigging 0/1 done
| 1 set | Mounting structure | site-specific, not derived; carries 1,272 kg, about 34 kg/m² |
Power 0/2 done
| 12 pcs | House circuits (16 A / 230 V) | 28.9 kW max · ~11.6 kW typical content · from the building's board | ||
| 623 pcs | TRUE1 jumpers | panel-to-panel, incl. 10% spare |
Data & control 0/3 done
| 14 pcs | NovaStar VX1000 | 136/140 ports used (A and B, 7 + 7 units) | ||
| 136 pcs | Cat6A home runs, ~40 m | run + height + 5 m loop, A and B | ||
| 636 pcs | Cat6 panel jumpers | incl. 10% spare |