RigPlan.app

Dahua DHI-PHGOA2.97-PH · 2.976 mm

This sheet gives the datasheet figures for the Dahua DHI-PHGOA2.97-PH, a 2.976 mm LED panel in a 500 × 500 mm cabinet, with a worked example wall and a calculator preloaded with it. Change columns and rows to get resolution, power draw, circuits, the data wiring plan, rigging quantities and the complete pack list.

Spec sheet from the manufacturer datasheet

ManufacturerDahua, PH series
Pixel pitch2.976 mm
Cabinet size500 × 500 × 77 mm
Pixels per cabinet168 × 168 (28,224 px)
Weight9 kg (36 kg/m²)
Max power, full white170 W (680 W/m²)
Typical power50 W
Refresh rate3,840 Hz
Brightness4,500 nits
Viewing angle (H / V)160° / 90°
Max hangnot published by manufacturer
Hanging bar weightnot published by manufacturer
Panels per dolly8 (our packing assumption)

Source: Dahua: DHI-PHGOA2.97-PH technical specifications, retrieved 2026-09-17. Outdoor fixed-install cabinet, the maker’s general outdoor fixed series, SMD1515, frontandrear maintenance, wall mounted, floor mounted, front IP68/rear IP66. Page gives 680/200 W/m² maximum and average at 4,500 nits, 3,840 Hz and 9 kg ±0.5 per cabinet. No hanging limit is published, so the hang figure is a placeholder.

Worked example: a 16 × 9 wall (16:9)

16 columns by 9 rows of this tile makes a 8.00 × 4.50 m wall, the closest this cabinet gets to 16:9, at 2,688 × 1,512 pixels (4.06 MP): 144 panels plus 8 spares at the one-off rate. It weighs about 1,296 kg, carried by the structure it is mounted on.

On European power it draws 24.5 kW at full white (7.2 kW on typical content), which at an 80% derate is 9 × 16 A / 230 V circuits. Data comes to 8 runs at up to 18 panels per port, worst run 78% loaded, fitting 2 × NovaStar VX1000 with looped A and B data. Every figure is derived by the calculator below. Change the numbers for your own wall.

R178%R278%R378%R478%R578%R678%R778%R878%wall-mounted: the structure carries 1,296 kg8.00 m (2,688 px)4.50 m (1,512 px)24.5 kW max · 9× 16 A / 230 V · 8 runs on 2× NovaStar VX1000

Main: 16 × 9 Dahua DHI-PHGOA2.97-PH

Size
8.00 × 4.50 m
Diagonal
361 in
Area
36.0 m²
Resolution
2,688 × 1,512 px
Pixels
4.06 M px
Panels
144 + 8 spares
Weight
1,296 kg panels only
Power
24.5 kW max, 7.2 kW typical, 9 circuits
Data
8 runs on 2 processors at 60 Hz 8-bit

This is a live example. Change the panel and the size in the steps and every figure recomputes.

RigPlan.appPrinted
Summary
1 wall · 230 V / 16 A circuits · 60 Hz 8-bit · wall-mounted
MainDahua DHI-PHGOA2.97-PH16 × 98.00 × 4.50 m · 361 in2,688 × 1,512 pxwall-mounted
Panels
144 + 8 spares
Weight
1,296 kg panels only
Power
24.5 kW max, 7.2 kW typical, 9 circuits
Data
8 runs on 2 processors at 60 Hz 8-bit

The install list, the data wiring and power run plans, the cable tags and the system sheet print with a Solo account: rigplan.app/pricing

Data wiring 8 runs · up to 18 panels per run at 80% · worst 78% · 2× NovaStar VX1000 · fed from the top

Display connection file 🔒 The file NovaLCT loads under Screen Connection, Load from File; the receiving card file still comes from the maker.

Run 1Columns 1 to 218 panels · 78% of port
Run 2Columns 3 to 418 panels · 78% of port
Run 3Columns 5 to 618 panels · 78% of port
Run 4Columns 7 to 818 panels · 78% of port
Run 5Columns 9 to 1018 panels · 78% of port
Run 6Columns 11 to 1218 panels · 78% of port
Run 7Columns 13 to 1418 panels · 78% of port
Run 8Columns 15 to 1618 panels · 78% of port

Power runs 9 circuits · up to 16 panels/circuit · 24.5 kW max · 1× distro

Circuit 1Row 1, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L1
Circuit 2Row 2, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L2
Circuit 3Row 3, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L3
Circuit 4Row 4, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L1
Circuit 5Row 5, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L2
Circuit 6Row 6, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L3
Circuit 7Row 7, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L1
Circuit 8Row 8, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L2
Circuit 9Row 9, fed left to right (rear)16 panels · 2,720 W · 92% · Distro 1 · L3
PatchDistro 1: circuits 1 to 9 (L1×3 L2×3 L3×3)

The rules behind every number

Every quantity above is derived from the rules below, written with working AV techs and corrected as they red-pen them.

  1. openSpare panels: 5% of wall count, minimum 2 (wall-mounted, spares kept on site at the one-off rate).
  2. ✓ confirmedWall-mounted: the wall or structure carries the panels, 1,296 kg over 8.00 × 4.50 m, about 36 kg/m² plus your fixing hardware. Nothing hangs from the panels, so the hang limit does not apply. The structure is designed for the site and is not derived here; no bumpers, points, ground support, distros, cases or truck are listed.
  3. ✓ confirmedCircuits sized on max load (full white) at 80% derate: 17 panels per 16 A / 230 V circuit (170 W/panel). Typical draw shown separately for the venue/generator ask.
  4. ✓ confirmedPower runs follow the connectors: in one side, out the other, gendered plugs, jumpers as short as the maker can get away with. Vertical works both ways, sideways only one hop to the right (rear view), so a run may snake up and down across adjacent columns, but never left and right. Full rows fed left to right need 9 circuits against 16 vertical; rows win here.
  5. openPower for a permanent install comes as 9 house circuits from the building's distribution board; no distro or feeders are listed. TRUE1 jumpers = panels − runs, +10% spare.
  6. ✓ confirmedRuns are load-balanced: panels split evenly across the circuits a shape needs (12+12, never 18+6) so every main-in pulls about the same. Phases are a suggested round-robin L1 to L3 within each distro.
  7. ✓ confirmedExact-pixel mapping (NovaStar VX1000): a port carries only the panels wired to it, and data snakes in any direction (unlike power). Wiring follows whole columns as vertical serpentines, numbered from the left seen from the rear, the natural reading order when patching, with every run capped at 80% of 650 k px per 1G port at 60 Hz 8-bit (threshold, refresh and depth adjustable): at most 18 panels per run, giving 8 runs, each looped back to a B port on a second unit, worst run 78%. Loads balance evenly across runs. Capacity is the sheet figure at 8-bit; refresh scales as 60/Hz. No sheet publishes a per-port width cap; the MX40 Pro’s minimum load width is applied where it bites. Correct me with measured figures.
  8. ✓ confirmedRedundancy defaults off. Rental shows rarely run looped data; it is primarily a critical-installation feature. Turning it on gives every run a B loop from a second unit, so the processor count doubles.
  9. openData enters each run at the top of its first column and snakes on from there, so the drawing, the cable tags and the connection file all start at that end. The entry end is a choice per wall; the runs, ports and processors stay the same either way.
  10. openHome runs cut at run distance + wall height + 5 m service loop.
  11. openProcessors are checked on two limits: port count and total pixel capacity (capacities placeholder).
  12. ✓ confirmedProcessor list defaults to NovaStar (VX1000 first, UHD Jr / MCTRL / MX / VX family). Rental houses rarely run Brompton; it stays available for the shops that do. All figures verified against manufacturer spec sheets.
  13. openElectronics spares: 1 receiving card per 25 panels, 1 PSU per 25, minimum 1 each.

Cable tags 296 tags · 8 data runs · 9 circuits

One label per cable, both ends named, in the order the runs are wired: cabinets as column and row seen from the rear, c1r1 top left. Print them, or copy the list as CSV for a label printer.

Copy tags as CSV 🔒

The tag list, your own label format, and the CSV for a label printer are a Solo feature.

Install list

0/10 done

Panels 0/4 done

144 pcsDahua DHI-PHGOA2.97-PH tiles16×9 wall, 8.0×4.5 m
8 pcsSpare tilesone-off rate 5%
6 pcsSpare receiving cards
6 pcsSpare PSUs

Rigging 0/1 done

1 setMounting structuresite-specific, not derived; carries 1,296 kg, about 36 kg/m²

Power 0/2 done

9 pcsHouse circuits (16 A / 230 V)24.5 kW max · ~7.2 kW typical content · from the building's board
149 pcsTRUE1 jumperspanel-to-panel, incl. 10% spare

Data & control 0/3 done

2 pcsNovaStar VX100016/20 ports used (A and B, 1 + 1 units)
16 pcsCat6A home runs, ~40 mrun + height + 5 m loop, A and B
159 pcsCat6 panel jumpersincl. 10% spare
Planning aid. Rigging figures (points, loads, hardware) must be verified by a competent rigger before anything leaves the ground; panel and processor figures come from the manufacturers' datasheets and can change between revisions. Made with RigPlan, the free LED wall planner · rigplan.app

Other Dahua panels

The PH series has 7 panels: the Dahua PH series compared.

Where this panel sits

This sheet is listed under Dahua LED panels, the 2.8 to 2.9 mm pixel pitch class, fixed-install LED panels, outdoor LED panels, and the full panel database.

Compare with

How these numbers are derived: power and circuits, panels per data port, the pack list.